The Hub

The Hub Air-Air Heat Pump (ASHP)
Downstairs Room Temperature
Degrees Celsius
ASHP Elect. input
Estimate of carnot COP using estimated refrigerant temperatures only, and the Carnot equation. Defrosts (when they happen) will drop the estimate considerably
Sponsored by openenergymonitor.org
Carnot COP x45% = 5.0
Evaporating Refrigerant 9.8 C
Refrigerant Condensing 21.2 C
Only meaningful when green (running)
Electrical power of heat pump. Blue is all other electric use.
Total elec. power (ASHP + Other)
Outside 8.9 C
Other electric use
Room Temp. 17.5 C (mid)
Kitchen power
Room Temp. 17.1 C (by blower)
Refrigerant1 probe probably superheated. Refrigerant2 probe probably condensing temperature
see https://heatpumps.co.uk/the-hub/
ignore the first day or two of this graph
Energy, kWh per day
Room
Watts
Watts
Watts
Yellow = heat pump input (watts). . Blue = other electrical use (watts)
Heat Pump input and temperatures
The overnight blue shows fridges and freezers. The spikes are the freezer defosting
Kitchen kWh per day
Hover mouse over bars to read values. The Total is all electricity, including heat pump and kitchen